Model # HFP 100, Low Temperature Rise Separated Combustion Outdoor Gas Duct Furnaces
Item # HFP 100 — Model # HFP 100, Low Temperature Rise Separated Combustion Outdoor Gas Duct Furnaces
Power Exhausted (HFP) The outdoor gas duct furnace was design to be the primary heating source for a building and is certified for, non residential, commercial applications only. These furnaces are power vented eliminating any effect of an erratic chimney. Available in 11 models sizes from 75.000 to 400,000 btu/hr for either natural or propane gas operation. The airflow direction can be specified when ordering the unit. This duct furnace is certified for location downstream from the dehumidifier and has holes to drain any condensate that may flow onto the roof. There are many other options available including various types of gas control valves to suit specific requirements.
If you cannot find the product you need, please let us know what your requirements are by contacting us.
Power Exhausted (HFP) The outdoor gas duct furnace was design to be the primary heating source for a building and is certified for, non residential, commercial applications only. These furnaces are power vented eliminating any effect of an erratic chimney. Available in 11 models sizes from 75.000 to 400,000 btu/hr for either natural or propane gas operation. The airflow direction can be specified when ordering the unit. This duct furnace is certified for location downstream from the dehumidifier and has holes to drain any condensate that may flow onto the roof. There are many other options available including various types of gas control valves to suit specific requirements.
Standard Features
- 18 gauge aluminized steel cabinet with a baked-on polyester powder paint finish on exterior casing parts
- 409 stainless steel drip pan
- 409 stainless steel heat exchanger and burners
- All units a minimum of 80% thermally efficient
- C.S.A. certification for use in the US and Canada
- Certified to 3.0" W.C. external static pressure
- Combination combustion air/exhaust vent cap
- ETL certification
- High limit safety control
- Left side (when looking into the discharge) access to burner and gas controls with slide-out burner drawer
- Natural gas input
- Power exhaust
- Rail type mounting base for slab installation
- Separate line voltage and low voltage terminal strips
- Side or bottom gas connection access
- Single 115V control step down transformer with 24V gas control circuit
- Single stage intermittent pilot with continuous retry control system for operation on natural gas.
- Two-stage gas valve
Optional Features
- Adjustable differential air flow proving system
- Building management compatible gas controls for modulation control using a 0-10 VDC or 4-20 mA input
- Control relay - double pole, double throw
- Control step down transformers for 208/230V/1Ph and 208/230/460/575V/3Ph
- Fan delay timer
- High and/or low gas pressure switches
- Manual reset high limit switch
- Mechanical modulation and electronic modulation controls for natural gas
- Multiple furnace electronic amplifier for controlling up to 4 duct furnaces with one discharge air sensor
- Right side access to burner and gas controls
- Single stage intermittent pilot with lockout control system for operation on propane gas
- Supply air fire stat
- Timed freeze protection
- Two-stage, mechanical modulation, and electronic modulation controls for propane gas
Gas Connection Pipe Size
1/2 in
Approximate Unit Net Weight
235 lb
Approximate Unit Shipping Weight
315 lb
Footnotes
1 Dimensions are subject to change without notice
Footnotes
1 Dimensions are subject to change without notice
Footnotes
1 Dimensions are subject to change without notice
Footnotes
1 Dimensions are subject to change without notice
Btu/Hr Input
100,000
Btu/Hr Output
80,000
20°F Air Temperature Rise
3704 CFM
25°F Air Temperature Rise
2963 CFM
30°F Air Temperature Rise
2469 CFM
35°F Air Temperature Rise
2116 CFM
40°F Air Temperature Rise
1852 CFM
45°F Air Temperature Rise
1646 CFM
50°F Air Temperature Rise
1481 CFM
55°F Air Temperature Rise
1347 CFM
60°F Air Temperature Rise
1235 CFM
Air Temperature and External Static Pressure Limits
The maximum allowable discharge air temperature is 150ºF. The maximum allowable air temperature rise for Low Air Temperature Rise Outdoor Units is 60ºF. The maximum allowable air temperature rise f
Note
115/60/1 Supply Voltage
1.40 A
Total Unit Amp Draw
The total unit amp draw is a combination of the control step down transformer and the power exhauster motor. The control step down transformer includes damper actuators, ignition controllers, gas val
Dimensions - B
34.46 in
Dimensions - C (Duct Height)
18.98 in
Dimensions - D (Duct Height)
17.69 in
Dimensions - F
36.11 in
Dimensions - G
28.00 in
Dimensions - Q
10.95 in
Dimensions - R
7 in
Footnotes
1 Dimensions are subject to change without notice
Product Specifications
Low Temperature Rise Separated Combustion Outdoor Gas Duct Furnaces
Low Temperature Rise Separated Combustion Outdoor Gas Duct Furnaces
Low Temperature Rise Separated Combustion Outdoor Gas Duct Furnaces
Low Temperature Rise Separated Combustion Outdoor Gas Duct Furnaces
Low Temperature Rise Separated Combustion Outdoor Gas Duct Furnaces
Low Temperature Rise Separated Combustion Outdoor Gas Duct Furnaces
Low Temperature Rise Separated Combustion Outdoor Gas Duct Furnaces
Low Temperature Rise Separated Combustion Outdoor Gas Duct Furnaces
Low Temperature Rise Separated Combustion Outdoor Gas Duct Furnaces
Low Temperature Rise Separated Combustion Outdoor Gas Duct Furnaces
Center Bonded Mounts STA Series
Dehumidifiers
Control Systems
Remote Condensers
Add-On Duct Heaters
We’ve only looked at three common problems here, but there are a host of other issues that can cause dehumidifier malfunctioning.
To read more about what can go wrong with dehumidifiers and learn how to fix problems quickly and efficiently, download our free dehumidifier troubleshooting guide today.
Download our Free Troubleshooting Guide