Model # DCA3600YV, Non Water Heating Assist Dehumidifier
Item # DCA3600YV — Model # DCA3600YV, Non Water Heating Assist Dehumidifier
Air Cooled, non water heating assist dehumidifiers are used when there is a primary pool and spa water heating source such as a hot water boiler in place.Typical applications would include, but be limited to, small pool surface area projects or in coldclimates or both.
If you cannot find the product you need, please let us know what your requirements are by contacting us.
Available Model Configurations
DCA3600YV: Air Cooled
DCA3600YV-CT: Water Cooled
Standard Features
- Listed to UL 60335-2-40
- 3 Year Parts Warranty
- Single Refrigeration Circuit
- Single Scroll Compressor
- Powder Coated, Galvannealed Steel Cabinet
- Low Ambient Head Pressure Control
- Remote Condenser Ready
- Rifle Tube Refrigeration Coils
- TEFC High Efficiency Blower Motor
- Stainless Steel Condensate Drain Pan
- Standard Microprocessor Control System
- Motorized Evaporator Bypass Damper
- ElectroFin Coated Coils
Optional Features
- Right Side Return Air
- Horizontal Discharge (Not Field Convertible)
- Extended Surface Filters 2" & 4"
- Outdoor Make Up Air Flanged Opening ( Damper & Filter by Others)
- External Static Upgrade
- Water Cooled Condenser For Water Heating Or A/C
- Remote Ready Delete
- Defrost Timer Package
- Control Options
- Space Heating Options Available
- Other Options Available
CFM
3600
Compressor Type
Scroll
Drain Connection
1" Bar Drain
External Static Pressure
1.00" H2O
Filter (Quantity: 4)
16" x 20" x 1" Fiberglass
Hot Gas Outlet [O.D.] (up to 50')³
1.125 in
Liquid Inlet [O.D.] (up to 50')³
0.625 in
Moisture Removal @ 82°DB / 50% R.H.¹
34.1 LB/HR
Moisture Removal @ 82°DB / 60% R.H.¹
43.2 LB/HR
Nominal Tonnage
7.6
Refrigerant
R-454B (Factory Charged 45 lbs.)
Sensible Cooling @ 82°DB / 50% R.H.²
51.3 MBH
Sensible Cooling @ 82°DB / 60% R.H.²
45.5 MBH
Weight
950 LB
Note
Ratings are subject to change without notice
Footnotes
1 Reheat Mode assuming 1050 BTU/lb
2 Cooling Mode with Remote Condenser at 95 °F
3 Over 50 ft contact factory
Available Voltage/Phase
208/230-3-60
460-3-60
575-3-60
Compressor @ 208/230-3-60
89900 BTU
27.6 RLA
203 LRA
Blower Motor @ 208/230-3-60
3.0 hp
9.0 FLA
Unit FLA @ 208/230-3-60
38.3
Maximum Fuse Size @ 208/230-3-60
60
Minimum Circuit Ampacity @ 208/230-3-60
45.2
Operating Power @ 208/230-3-60
9.40 kW
Compressor @ 460-3-60
89900 BTU
14.1 RLA
98 LRA
Blower Motor @ 460-3-60
3.0 hp
4.2 FLA
Unit FLA @ 460-3-60
19.1
Maximum Fuse Size @ 460-3-60
30
Minimum Circuit Ampacity @ 460-3-60
22.6
Operating Power @ 460-3-60
9.22 kW
Compressor @ 575-3-60
89900 BTU
11.6 RLA
84 LRA
Blower Motor @ 575-3-60
3.0 hp
3.3 FLA
Unit FLA @ 575-3-60
15.6
Maximum Fuse Size @ 575-3-60
25
Minimum Circuit Ampacity @ 575-3-60
18.5
Operating Power @ 575-3-60
9.17 kW
Manuals & Guides
Warranty & Compliance
Product Specifications
Technical Drawings
Revit
CAD
Center Bonded Mounts STA Series
Dehumidifiers
Control Systems
Remote Condensers
Add-On Duct Heaters
We’ve only looked at three common problems here, but there are a host of other issues that can cause dehumidifier malfunctioning.
To read more about what can go wrong with dehumidifiers and learn how to fix problems quickly and efficiently, download our free dehumidifier troubleshooting guide today.
Download our Free Troubleshooting Guide